Heat pump WH-MXC09J3E5
Product description
Medium temperature heat pump, Aquarea High Performance, Single (monobloc- MXC), Generation J. Heating and Cooling, with ecological Coolant R32!
"HEATING 9 kW COOLING 9kW"
Features
Energy efficiency: A+++
Stable power down to -20 0C
Single-phase
With INVERTER pump, line filter and 10 litres expansion tank.
With 3kW resistors (optional use)
With electronic control - room thermostat
With Wifi & BMS connectivity
Technical characteristics
Additional information
Technical characteristics
External unit code | KIT-WXC16H9E8 | |
---|---|---|
Heating efficiency / COP (At +7 °C, water outlet 35 °C | kW / COP | 9,00 / 5,08 |
Heating efficiency / COP (At +7 °C, water outlet 55 °C | kW / COP | 9,00 / 3,08 |
Heating efficiency / COP (At +2 °C, water outlet 35 °C) | kW / COP | 9,00 / 3,81 |
Heating efficiency / COP (At +2 °C, water outlet 55 °C) | kW / COP | 9,00 / 2,54 |
Heating efficiency / COP (At -7 °C, water outlet 35 °C) | kW / COP | 9,00 / 3,08 |
Heating efficiency / COP (At -7 °C, water outlet 55 °C) | kW / COP | 9,00 / 2,12 |
Cooling efficiency / EER (At 35 °C, water outlet 7 °C) | kW / EER | 9,00 / 3,18 |
Cooling efficiency / EER (At 35 °C, water outlet 18 °C) | kW / EER | 9,00 / 4,62 |
Heating in mild climate (W 35 °C / W 55 °C) Seasonal energy efficiency |
hs % | 195 / 140 |
Heating in mild climate (W 35 °C / W 55 °C) Energy class |
SCOP | A+++ / A++ |
Heating in hot climates (W 35 °C / W 55 °C) Seasonal energy efficiency |
hs % | 256 / 171 |
Heating in hot climates (W 35 °C / W 55 °C) Energy class |
SCOP | A+++ / A+++ |
Heating in cold climates (W 35 °C / W 55 °C) Seasonal energy efficiency |
hs % | 169 / 127 |
Heating in cold climates (W 35 °C / W 55 °C) Energy class |
SCOP | A++ / A++ |
Noise levels (Heating) | dB(A) | 65 |
Dimensions (H x W x D) | mm | 1 410 x 1283 x 320 |
Net weight | kg | 140 |
Refrigerant (R32) / CO2 equivalent | kg / T | 1,60 / 1,080 |
Hydraulic circuit connections | Inch | R 1¼ |
Class A (Number of speeds) | Variable speed | |
Class A cycler (Consumption (Min/Max) | W | 32 / 102 |
Heating water supply (ΔT=5 K. 35 °C) | l/min | 25,8 |
Built-in electrical resistance power | kW | 3 |
Consumption (Heating - Cooling) | kW | (1,77 / 2,83) |
Current intensity in operation and at start-up (Heating - Cooling) |
A | (8,3 / 13,1) |
Current 1 | A | 29,0 |
Current 2 | A | 13,0 |
Proposed electrical fuse, supply 1/2 | A | 30 / 30 |
Desired cable length, supply 1/2 | mm² | 3 x 4,0 or 6,0 / 3 x 4,0 |
Operating range- outdoor temperature (Heating) |
°C | 10 ~ +43 |
Operating range- outdoor temperature (Cooling) |
°C | -20 ~ +35 |
Water outlet (Heating / Cooling) | °C | 20 ~ 65 / 5~20 |