Heat pump WH-MHF09G3E5
Product description
High temperature heat pump, Aquarea HT, Single (monobloc - MHF), Generation G. Heating, with Coolant R407C
HEATING 9 kW
Features
Energy efficiency: A+++
Single-phase
With INVERTER pump and 10 litres expansion tank.
With 3kW resistors (optional use)
With electronic control
Technical characteristics
Additional information
Technical characteristics
External unit code | WH-MHF09G3E5 | |
---|---|---|
Heating efficiency / COP (At +7 °C, water outlet 35 °C | kW / COP | 9,00 / 4,64 |
Heating efficiency / COP (At +7 °C, water outlet 55 °C | kW / COP | 9,00 / 2,48 |
Heating efficiency / COP (At +2 °C, water outlet 35 °C) | kW / COP | 9,00 / 3,45 |
Heating efficiency / COP (At +2 °C, water outlet 55 °C) | kW / COP | 9,00 / 2,06 |
Heating efficiency / COP (At -7 °C, water outlet 35 °C) | kW / COP | 9,00 / 2,74 |
Heating efficiency / COP (At -7 °C, water outlet 55 °C) | kW / COP | 9,00 / 1,79 |
Heating in mild climate (W 35 °C / W 55 °C) Seasonal energy efficiency |
hs % | 153 / 125 |
Heating in mild climate (W 35 °C / W 55 °C) Energy class |
SCOP | A++ / A++ |
Heating in hot climates (W 35 °C / W 55 °C) Seasonal energy efficiency |
hs % | 191 / 156 |
Heating in hot climates (W 35 °C / W 55 °C) Energy class |
SCOP | A+++ / A+++ |
Heating in cold climates (W 35 °C / W 55 °C) Seasonal energy efficiency |
hs % | 137 / 116 |
Heating in cold climates (W 35 °C / W 55 °C) Energy class |
SCOP | A+ / A+ |
Noise levels (Heating) | dB(A) | - |
Dimensions (H x W x D) | mm | 1 410 x 1283 x 320 |
Net weight | kg | 151 |
Refrigerant (R32) / CO2 equivalent | kg / T | 1,92 / 3,406 |
Hydraulic circuit connections | Inch | R 1¼ |
Class A (Number of speeds) | 7 | |
Class A cycler (Consumption (Min/Max) | W | - |
Heating water supply (ΔT=5 K. 35 °C) | l/min | 25,8 |
Built-in electrical resistance power | kW | 3 |
Consumption (Heating - Cooling) | kW | 1,94 |
Current intensity in operation and at start-up (Heating - Cooling) |
A | 9,3 |
Current 1 | A | 28,5 |
Current 2 | A | 13,0 |
Proposed electrical fuse, supply 1/2 | A | 30 / 30 |
Desired cable length, supply 1/2 | mm² | 3 x 4,0 or 6,0 / 3 x 4,0 |
Operating range- outdoor temperature (Heating) |
°C | -20 ~ +35 |
Water outlet (Heating) | °C | 25 ~ 65 |